Oil/water alarm unit ÖWWG 3

Afriso Oil/water alarm unit ÖWWG 3
Afriso Oil/water alarm unit ÖWWG 3
Afriso Oil/water alarm unit ÖWWG 3
Afriso Oil/water alarm unit ÖWWG 3
Afriso Oil/water alarm unit ÖWWG 3
Afriso Oil/water alarm unit ÖWWG 3
Afriso Oil/water alarm unit ÖWWG 3
Data sheet Oil/water alarm unit ÖWWG 3
Afriso Data sheet Oil/water alarm unit ÖWWG 3

Versions

Part no. Remember
Oil/water alarm unit ÖWWG 3 AC 100-240 V, Kabellänge 3,2 m 44510
Oil/water alarm unit ÖWWG 3 AC 100-240 V, Kabellänge 10 m 44494
Oil/water alarm unit ÖWWG 3 AC/DC 15–40 V, Kabellänge 3,2 m 44488
Probe for ÖWWG 3 year of manufacture 09/2013 and later Cable length 3.2 m 44516
Probe for ÖWWG 3 year of manufacture 09/2013 and later Cable length 10 m 44484
Probe for ÖWWG 3 year of manufacture 09/2013 and later Cable length 25 m 44482
Probe for ÖWWG 3 up to year of manufacture 08/2013 Cable length 3.2 m 44481
Probe fuse 44495
Mains fuse 10820
EnOcean® wireless module TCM 320 78082

Blue part no. = in-stock items

Description Format Language Download / Link
Data sheet Oil/water alarm unit ÖWWG 3 Data sheet PDF
Afriso Data sheet Oil/water alarm unit ÖWWG 3
Oil/water alarm unit ÖWWG 3 Operating instructions PDF
Afriso Oil/water alarm unit ÖWWG 3
Flyers Alarm units PDF
Afriso Flyers
WATCHDOG-LINE alarm units Alarm units PDF
Afriso WATCHDOG-LINE alarm units
Oil/water alarm unit ÖWWG 3 Konformitätserklärung PDF
Afriso Oil/water alarm unit ÖWWG 3
The oil/water alarm unit in a wall mounting housing triggers visual and audible alarms in the event of accumulations of liquids which can be caused by tank leaks, backflow, flooding, etc. ÖWWG 3 consists of a control unit with visual/audible alarm, Test and Acknowledge buttons as well as a flexible PTC thermistor probe. The probe is mounted at the lowest point of the area to be monitored. Alarm is triggered when there is contact with escaped liquid. The audible alarm can be muted with the Acknowledge button. The visual alarm remains active until the leak has been removed. The Test button allows you to simulate an alarm condition in order to perform a function test. The self-monitoring probe triggers an alarm if it is damaged. The voltage-free relay contact is provided for connection of additional alarm equipment (such as additional alarm unit ZAG 01). ÖWWG 3 is suitable for panel mounting with a mounting frame. A sealing kit (IP 54) is available for rough application conditions. Alarm units with the EnOcean-ready label can be integrated into your existing building automation systems, for example, AFRISO smart home, at a later point in time. To do so, plug the EnOcean® wireless module into the EnOcean® interface (PCB of the device).
Operating temperature range
Ambient:
-5/+40 °C
Storage:
-10/+60 °C
Probe
L x ⌀:
57 x 14 mm
Cable length:
3.2 m, 10 m or 25 m
Supply voltage
AC 100 – 240 V
AC/DC 15 – 40 V
Nominal power
10 VA
Switching output
Relay contact:
1 x voltage-free changeover contact
Contact rating:
Max. AC 250 V, 2 A
Alarm sound
Min. 70 dB(A)
Housing (Wall mounting housing made of impact-resistant plastic (ABS))
W x H x D:
100 x 188 x 65 mm
Weight:
600 g
Degree of protection:
IP 40 (EN 60529)
Approval
DIBt: Z-65.40-339
Scope of delivery
  • Control unit
  • PTC thermistor probe
Option
  • EnOcean<sup>®</sup> wireless module (can be retrofitted)