Level probe 76 A for overfill prevention system (WHG)

Afriso Level probe 76 A for overfill prevention system (WHG)
Afriso Level probe 76 A for overfill prevention system (WHG)
Afriso Level probe 76 A for overfill prevention system (WHG)
Data sheet level probe 76 A for overfill prevention system (WHG)
Afriso Data sheet level probe 76 A for overfill prevention system (WHG)

Versions

Length Part no. Remember
Level probe 76 A 100 mm 53225
Level probe 76 A 200 mm 53217
Level probe 76 A 300 mm 53220
Level probe 76 A 400 mm 53207
Level probe 76 A 500 mm 53209

Blue part no. = in-stock items

Description Format Language Download / Link
Data sheet level probe 76 A for overfill prevention system (WHG) Data sheet PDF
Afriso Data sheet level probe 76 A for overfill prevention system (WHG)
Approved as part of an overfill prevention system together with level transducer UFS 01, NB 220 H and NB 220 QS. The level probe type 76 A consists of a probe tube with a stainless steel-encapsulated PTC thermistor sensor at the lower end, a junction box and a screw fitting. Tube length 100 to 3,000 mm in increments of 100 mm. Standard lengths up to 500 mm. The overfill prevention system must be set up in such a way that a visual alarm and a sufficiently loud audible alarm are triggered when the maximum permissible level is reached.
Material
Junction box:
Brass
Probe tube:
Stainless steel 304 or 316 Ti
Screw fitting:
Brass
PTC thermistor:
Stainless steel-encapsulated
Operating temperature range
Medium:
-25/+50 °C
Degree of protection
IP54 (EN 60529)
Approval for construction products
DIBt: Z-65.11-193