Images 2
Back
Transducer MFU 12 2 voltage-free changeover contacts | 53722
multifunctional transducer MFU 12/14
manufactured goods
- Universal input (current, voltage, resistance)
- integrated supply voltage for 2/3-wire transmitter
- 2 analogue outputs
- 2 or 4 additional contact outputs
- Programming interface
- Universal power supply unit
The digital multi-purpose transducers are freely programmable digital transducers with two analogue outputs and up to 4 relays.
Current up to 20 mA (also bipolar), voltage up to 10 V (also bipolar) or a three-wire technology potentiometer are possible input signals. In addition, a supply for 2-wire or 3-wire transmitters is integrated. The inputs are galvanically isolated from the voltage and the outputs. The two analogue outputs can be used simultaneously.
- Display
- multi-line LCD,
42 x 64 Pixel,
multicolour backlight,
Hintergrundbeleuchtung abschaltbar
- Range
- 0 to 9,999 digits,
start and end values configurable as required,
freie Skaliereinheit,
3 languages (German, English, French)
- Accuracy
- ± 0.2 % of maximum value
- Resolution
- inputs:
- 13 Bit
- outputs:
- 10 Bit
- inputs
- Current:
- max. -20.4/+20.4 mA, adjustable as required
- voltage:
- max. -10.2/+10.2 V, adjustable as required
- potentiometer:
- 0.1/100 kOhm, adjustable as required
- transmitter supply:
- DC 19.5 − 24.5 V
- Analogue output 1 (current)
- max. 0/4–20.4 mA, adjustable as required
- galvanically isolated from input
- Analogue output 2 (voltage)
- max. 0/2–10.2 V, adjustable as required
- galvanically isolated from input
- switching outputs
- MFU 12: 2 voltage-free changeover contacts
- Configurable as required
- Contact rating:
- max. AC 250 V
- configurable functions: energising/de-energising, hysteresis, window or trend function wählbare Anzugs- und Abfallverzögerungen
- Linearisation
- via 24 free x/y points on characteristic curve Kennlinienmodus Tabelle, Zylinder, Kugel
- additional functions
- Alarm message in the case of missing or defective sensor Lupenfunktion, Spreizung, Inversmodus, Trendanzeige, Lernfunktionen automatic or manual simulation mode Verriegelung der Parametrierung über Editiersperre Programming interface
- Supply voltage
- AC 50 − 253 V
- DC 20 − 253 V
- Housing
- DIN rail housing
- W x H x D:
- 33 x 110 x 128 mm
- screw terminals removable