Twin thermostats with housing GDT

Afriso Twin thermostats with housing GDT
Afriso Twin thermostats with housing GDT
Afriso Twin thermostats with housing GDT
Afriso Twin thermostats with housing GDT
Data sheet Twin thermostats with housing GDT
Afriso Data sheet Twin thermostats with housing GDT

Versions

Adjustment Operating range Switching point Stem length Part no. Remember
Twin thermostat with housing GDT/8HR Internal/external 100 mm 67447X
Twin thermostat with housing GDT/8RS Fixed/external 0/90 °C 100 °C 150 mm 67454AX
Twin thermostat with housing GDT/8RS Fixed/external 0/90 °C 100 °C 200 mm 67454BX
Twin thermostat with housing GDT/8RS Fixed/external 0/90 °C 100 °C 100 mm 67453X
Twin thermostat with housing GDT/TTCA Internal/external 280 mm 67640

Blue part no. = in-stock items

Description Format Language Download / Link
Data sheet Twin thermostats with housing GDT Data sheet PDF
Afriso Data sheet Twin thermostats with housing GDT
The temperature measured at the probe causes a change in the volume of the measuring liquid. Electrical switching is triggered by the force acting. The thermowell allows for direct installation pressure-tight tanks.
Type
GDT/TLSC
Tolerance
GDT/8HR:
± 3 K
GDT/8RS:
+0 K/-6 K at ambient temperature 20 °C
GDT/TTCA:
± 3 K
Switching differential
∆T 4 ± 1 K
Setting
GDT/8HR:
Internal/external
GDT/8RS:
Fixed/external
GDT/TTCA:
Internal/external
Probe
Copper
∅ 16 mm
Length:
100, 150, 200, 280 mm
Probe element
Liquid-filled
Operating temperature range
Probe:
Max. 125 °C
Housing:
Max. 80 °C
Operating pressure at thermowell
Max. 4 bar
Housing
Plastic (PVC), grey (RAL 7035)
Cable entry
Plastic (PVC), black
M20 x 1.5
Degree of protection
IP40 (EN 60529)
Time constant
DIN-tested
DIN EN 14597:2012-09
Registration number:
TR/STB 1231
Electrical switching contact
2 x changeover contact
Contact rating
NC:
AC 250 V, 10 (2.5) A
NO: