Skip to main content

PrimoTherm® K 180-1 DN32

Heating pump assembly

  • pre-assembled, tightness-tested and heat-insulated assembly
  • compact design
  • available with high energy efficiency pump class A
  • easy, fast mounting

Heating pump assembly for use in non-mixed heating circuits, specially for storage tank charging. It connects the heating boiler and the pipe system.

Complete, pre-assembled and tightness-tested heating pump assembly with all required functional components, form-fit insulation and wall mounting unit. System connection: Primary end (consumer) G1¼ female
The pump line (flow/hot) consists of:
Combination valve with thermometer in the hand wheel (red mark, range 0/120 °C)
Ball valve below the pump, suitable for use of pumps with 2" x 180 mm
System connection G1¼ female (heating circuit)
The return line consists of:
Combination valve with thermometer in the hand wheel (blue mark, range 0/120 °C)
Pipe for length compensation with gravity brake
System connection (boiler) G2 with screw connection G1¼ female (easy mounting and adapter G1½ AB for use with boiler manifold)

opening temperature is reachedPumpPart no.
Heating pump assembly PrimoTherm® K 180-1 DN32Without circulation pump79501
Heating pump assembly PrimoTherm® K 180-1 DN32 GPGrundfos UPM3(K) HYBRID 32-70 180 (N)79503
Heating pump assembly PrimoTherm® K 180-1 DN32 WPWilo Para OPT 30-180/8-60/SC79504
  • in-stock items
  • manufactured goods

Axis distance
  125 mm
system connections
Boiler:
G1¼ IG
Heating circuit:
G1¼ IG
Operating temperature range
Medium:
max. 110 °C
System pressure
max. 10 bar
max. observe maximum pressure of circulation pumps used
Nominal size
DN 32
Flow coefficient Kvs
21 m³/h
Heat insulation
Polypropylene EPP
Dimensions
W x H x D:
248 x 480 x 170 mm
Circulation pump
Without circulation pump
Power input
Without circulation pump:
Without circulation pump:
Without circulation pump:
operating modes/settings
Without circulation pump:
Options
  • with high-efficiency pump EEI 0,2