Skip to main content
Back

TSA 14 FO | 79402

thermostatic actuator

in-stock items

  • First Open function
  • manual Re-Open function without power applied
  • Stroke indicator
  • supply voltage 24 V
  • control voltage 2-10 V
  • continuous control and monitoring of stroke position

For continuous control of hot water valves in heating and cooling circuits for highly demanding control tasks in building control systems. The actuator converts the electrical signal (2-10V) received from a room thermostat or a building control system into a valve stroke. Depending on the version, the supply voltage is DC (direct voltage) or AC (alternating voltage). The actuator is factory-opened (First Open function) so that the vales at the heating circuit manifold remain open during initial commissioning. This facilitates mounting as well as filling and flushing of the system since, at this point in time, the control system is usually not yet operative. The First Open function (FO) is automatically disabled as soon as the actuator is electrically connected and fully closed. The FO function can also be manually deactivated by lifting the stroke indicator with a screwdriver. When the stroke indicator is lifted, the "clip Re-Open" is relieved and disables the FO function. For servicing, the factory setting "open" of the actuator can be restored manually via the clip without power having to be applied. To do so, lift the stroke indicator with a screwdriver until the clip can be pushed below the stroke indicator. The pre-load of the stroke indicator keeps the clip in position and the FO function is active again.

Electro-thermostatic actuator with continuous control, with First Open and Re-Open functions, position indicator and control line 2–10 V. 2–10 V control line and union nut for direct connection to the valve or upper part of the valve. With spacer for closing dimension compensation and optimum adaptation to the valve to be controlled. Detection of closing dimension during initial commissioning.

functions
First Open and Re-Open functions (adjustable via "clip re-open"),
automatische Deaktivierung der First-Open-Funktion und Schließpunkterkennung durch Referenzfahrt bei Inbetriebnahme
Operating mode
closed when de-energised (NC)
Auslieferungszustand: Werkseitig geöffnet
control stroke
  4 mm
Closing dimension
  10.8 mm
Actuating force
  110 N
Connection
union nut M30 x 1.5 mm
Housing
Plastic PA 6, flame retardant
Degree of protection:
IP 54 (EN 60730-1)
cap:
white
Stroke indicator:
yellow
cable
3 x 0.25 mm2, white
Length   1 m
Operating temperature range
Operation:
max. 100 °C (at valve)
Ambient:
0/50 °C
Storage:
-25/+70 °C
ambient humidity:
< 85 % r.F., Non-condensing
Supply voltage
DC 24 V
Control voltage
DC 2–10 V
Power input
  1.1 W (Continuous operation)
Switch on power
  4.8 W
Inrush current
  200 mA
Protection class
III (EN 60730-1)
Dimensions (H x W x D)
68 x 40 x 56 mm
Weight
  120 g
Options
  • other control strokes
  • andere Spannungsbereiche
  • union nut M30 x 1.5 mm (brass, nickel-plated)