Skip to main content
Back

76 A | 53209

Standaufnehmer für Überfüllsicherung (WHG)

in-stock items

  • type approved in conjunction with the transducers UFS 01, NB 220 H and NB 220 QS as part of an overfill prevention system

Level probe for transducers as part of an overfill prevention system for stationary tanks and stationary-use tanks used to store water-polluting liquids with a flash point of > 55 ºC (see product description UFS 01 for list of substances).

Approved as part of an overfill prevention system together with level transducers UFS 01 and NB 220 H. The level probe type 76 A consists of a probe tube with a stainless steel-encapsulated PTC thermistor sensor at the lower end, a junction box and a screw fitting. Tube length 100 to 3,000 mm in increments of 100 mm. Standard lengths up to 500 mm. The overfill prevention system must be set up in such a way that a sufficiently loud audible alarm is triggered when the maximum permissible level is reached.

Material
junction box:
Brass
Probe tube:
stainless steel 304 or 316 Ti
Screw fitting:
Brass
PTC thermistor:
stainless steel-encapsulated
Process connection
Connection thread G¾
Operating temperature range
Medium:
-25/+50 °C
Degree of protection
IP 54 (EN 60529)
approval
DIBt: Z-65.11-185