Kapselfeder-Standardmanometer für Differenzdruck Typ D4

  • Measurement of extremely small differential pressures
  • robust design
  • static pressures up to 400 mbar
  • direct indication of the differential pressure
  • many customised versions available

For differential pressure measurement of non-corrosive, gaseous, dry media. Especially suitable for filter loss measurement in air conditioning and ventilation applications.
! For measuring gas or vapour, observe the table "Selection Criteria as per EN 837-2" (see appendix)!

housing ⌀Housingaccuracy classConnectionAusrichtungRangeTypePart no.
KP160DifD411160 mmStainless steel 3041,62 x G½B0/25 mbarKP160Dif D41135616411
KP160DifD411160 mmStainless steel 3041,62 x G½B0/40 mbarKP160Dif D41135617411
KP160DifD411160 mmStainless steel 3041,62 x G½B0/60 mbarKP160Dif D41135618411
KP160DifD411160 mmStainless steel 3041,62 x G½B0/100 mbarKP160Dif D41135619411
KP160DifD411160 mmStainless steel 3041,62 x G½B0/160 mbarKP160Dif D41135620411
KP160DifD411160 mmStainless steel 3041,62 x G½B0/250 mbarKP160Dif D41135621411
KP160DifD411160 mmStainless steel 3041,62 x G½B0/400 mbarKP160Dif D41135622411
  • in-stock items
  • manufactured goods

Type
D4
Nominal size
160 - 160
Function
The "plus" pressure (= high pressure) is applied to the inside of the diaphragm. The "minus" pressure (= low pressure) is applied to the inside of the pressure-tight housing. The pressure difference causes the diaphragm to change its shape, thus generating the movement required to measure the pressure. This displacement is picked up by the movement. The differential pressure is directly indicated by a pointer.
accuracy class
EN 837-3/6
≥ 0/25 mbar: 1,6
ranges (EN 837-3/5)
see ordering table
application area
static load:
Full scale value
dynamic load:
0.9 x full scale value
Overpressure safety
Full scale value
maximum static pressure
400 mbar
Operating temperature range
Medium:
max. 60 °C
Ambient:
-20/+60 °C
Temperature performance
Indication error when the temperature of the measuring system deviates from the normal temperature of 20 °C:
bei Temperaturzunahme ca. ± 0,6 %/10 K,
falling temperature approx. ± 0.6 %/10 K
vom jeweiligen Skalenendwert
Degree of protection
IP 66 (EN 60529)

Standard design

Connection
Brass: centre back, parallel, below each other
2 x G½B, SW22 (EN 837-3/7.3)
Measuring element (wetted part)
Capsule element, CuBe alloy
Movement (wetted part)
Brass
Zero correction
from the front
Seal (wetted part)
NBR (Perbunan)
Dial (wetted part)
Aluminium, weiß
Scaling black
Pointer (wetted part)
Aluminium, schwarz
Housing (wetted part)
Edelstahl 304
bayonet bezel
Edelstahl 304
Window (wetted part)
Kunststoff (PMMA)

854_017_0336-00.PDF