Skip to main content

STB

Sicherheits-Temperaturbegrenzer mit Kapillarleitung

  • ideal for heating and process industries
  • for protection against exceeding the maximum temperature
  • no external power supply
  • manual reset

There are many application areas for safety temperature cut outs in the heating and process industries. In conventional oil-fired or gas-fired boilers, these devices are used to monitor the boiler water. The safety temperature cut outs feature a manual reset button which must be actuated for unlocking.

If the temperature at the probe increases, the measuring liquid in the measuring system expands. If the temperature exceeds a critical value, the device triggers, the voltage-free contact switches and the system is set to a defined safe state. When the temperature has decreased by approx. 15 K, the device can be unlocked and the system resumes operation.

ContactSwitching pointSwitching pointcapillary lengthPart no.
Safety temperature cut outs STB LS1/971 F1Single100 °C1000 mm67273X
Safety temperature cut outs STB LS1/971 FUChangeover contact100 °C1000 mm67276X
Safety temperature cut outs STB LS1/971 FUChangeover contact100 °C1500 mm67277X
Safety temperature cut outs STB LS1/971 F1Single110 °C1500 mm67288X
Safety temperature cut outs STB LS1/971 FUChangeover contact75 °C1500 mm67585X
  • in-stock items
  • manufactured goods

Type
LS1
Switching point
see ordering table
Tolerance
+0 K/-6 K at 20 °C
Influence of ambient temperature
  0.25 °C/°C
Switching differential
∆T 15 ± 8 K
Fail safe
1 - 1
Probe
Copper
∅ 6.5 x 95 mm
Probe element
liquid-filled
Operating temperature range
Probe:
max. 125 °C
Housing:
max. 85 °C
Capillary tube
Cu capillary tube with PVC coating, black
Length:
1000 mm
Degree of protection
IP 00 (EN 60529)
Time constant
DIN-tested
DIN EN 14597:2012-09
registration number:
TR/STB 1211
electrical switching contact
Single
Contact rating
NC:
AC 250 V, 16 (2.5) A
NO:
AC 250 V, 0.5 A