Event reporting system EMS 442

 71020 object_image_64499imagemain_en
 VOR 21790 21800 21840 21850 112880 112890
 ANW 71020
 ANW 21790 21800 21840 21850 112880 112890
Data sheet Event reporting system EMS 442
AFRISO Data sheet Event reporting system EMS 442

Versions

Part no. Remember
Event reporting system EMS 442 90442
Setup of file on AFRISO Net server 90013
Monthly base fee per SIM card 90014

Blue part no. = in-stock items

Description Format Language Download / Link
Data sheet Event reporting system EMS 442 Data sheet PDF
AFRISO Data sheet Event reporting system EMS 442
Event reporting systems EMS: Operation via mobile phone - checklist 3 Event reporting systems DOC
AFRISO Event reporting systems EMS: Operation via mobile phone - checklist 3
Event reporting systems EMS: Operation via mobile phone - checklist 2 Event reporting systems DOC
AFRISO Event reporting systems EMS: Operation via mobile phone - checklist 2
Event reporting systems EMS: Operation via mobile phone - checklist 1 Event reporting systems DOC
AFRISO Event reporting systems EMS: Operation via mobile phone - checklist 1
GSM software for event reporting system EMS Event reporting systems ZIP AFRISO GSM software for event reporting system EMS
Event reporting systems EMS 442 Declaration of Conformity PDF
AFRISO Event reporting systems EMS 442
EMS 442 has 4 analogue and 4 digital inputs as well as 2 switching outputs (relay outputs) for connection of additional alarm equipment on site. EMS 442 sends alarm signals or results of continuous measurements to the mobile phone of the user or to the AFRISO Net server for documentation and further distribution. From the server, messages can be sent via Internet, text message or e-mail. The owner/operator can request information on the system status via mobile phone at any time. Measuring intervals, limit values and data transmission intervals can be adjusted as required.
Operating temperature range
Ambient:
-20/+50 °C
Supply voltage
AC 230 V
Sensor supply
4 x DC 24 V, max. 25 mA
Alarm inputs
4 analogue inputs 4–20 mA, active or passive
4 digital inputs, for voltage-free assignment
Switching outputs
Relay contacts:
2 voltage-free changeover contacts
Contact rating:
AC 250 V, 5 A, 500 VA
DC 24 V, 5 A, 100 W
Data transmission
GSM short message system (SMS) with integrated 2G/3G modem
900/1,800/2,100 MHz
Measuring intervals/data transmission intervals
Adjustable as required
Parameterisation/configuration
Via mobile phone
Housing
Wall mounting housing made of impact-resistant plastic (ABS)
W x H x D:
175 x 125 x 75 mm
Degree of protection
IP 65 (EN 60529)
Electrical connection
5 x cable gland M16 x 1.5
CE conformity
EMC Directive 2014/30/EU
RED Directive 2014/53/EU