Multi-channel process display MPA 10

 SAR 1060 object_image_96897imagemain_en
 BEF 1060
Data sheet multi-channel process display MPA 10
AFRISO Data sheet multi-channel process display MPA 10

Versions

Part no. Remember
Multi-channel process display MPA 10 31286

Blue part no. = in-stock items

Description Format Language Download / Link
Data sheet multi-channel process display MPA 10 Data sheet PDF
AFRISO Data sheet multi-channel process display MPA 10
The multi-channel process display MPA 10 is a combined display unit and data logger for control panel mounting. It provides up to 8 analogue inputs for standard signals. The inputs can be configured as a current inputs or a voltage inputs. Count values can be derived from the analogue signals by means of adjustable switching thresholds. It is possible to display scaled measured values with definable units. The measured values are displayed by means of configurable display elements such as numerical indication, bar chart, time diagram, maximum pointer or LEDs. The device is shipped with preconfigured standard display windows. All signals can be cyclically logged in the device memory. The logged data is saved to an internal microSD card as day files. These files can be saved to a USB flash drive at any time or downloaded via the network interface. The device is configured via the integrated web server of the network interface or the free configuration software. The various interfaces (RS 485/LAN) allow the device to be easily integrated into data networks so that measurement data can be displayed and logged in real time.
Operating temperature range
Ambient:
0/50 °C
Supply voltage
AC 50 – 253 V, max. 5 VA
DC 20 – 253 V, max. 3 W
Input resistance
Current:
< 65 Ohm
Voltage:
> 100 kOhm
Housing
W x H x D:
96 x 96 x 63 mm
Panel cut out
W x H:
90 x 90 mm
Weight
0.35 kg
Degree of protection
IP 20 (EN 60529)
Front:
IP 54 (EN 60529)
Electrical connection
Screw terminals removable
Interfaces
RS 232
AFRISO
Dimensions (in mm)
AFRISO
Dimensions (in mm)