Skip to main content
Back

leak detector LAG-13 KR with container and probe | 43500

leak detector LAG-13 KR

in-stock items

  • EU type examination certificate
  • Version as per German WHG/AwSV and BetrSichV
  • with fail-safe mode
  • for monitoring of aboveground, double-walled tanks

For double-walled tanks with liquid in the interstitial space. For monitoring water-polluting liquids with a flash point of > 55 °C stored aboveground. Approved for all suitable tanks under atmospheric conditions.
Since July 2003, the LAG-13 KR leak detector may only be used for replacements of existing systems at underground, double-walled tanks as a result of the reclassification of water-polluting liquids in Germany!

Leak detector class II (EN 13160-1/-3). The system consists of a control unit, a container for leak detection fluid (LAG container white) and a probe. Control unit with operating and alarm indicators, audible/visual alarm, test button and increased interference protection. The audible alarm can be muted with the Acknowledge button. The voltage-free relay contact is provided for connection of additional external alarm equipment (such as horns,) or an additional alarm unit ZAG 01. With fail-safe mode: Audible alarm if the probe fails. Suitable for panel mounting with a mounting frame; a sealing kit (IP 54) is available for rough application conditions. The LAG container serves as detection container and as expansion vessel at the same time. For aboveground tanks, the ratio between usable contents and total volume of leak detection fluid must be no more than 1:35. If the interstitial space has a greater volume, you must use additional containers.

Operating temperature range
Ambient:
-5/+50 °C
Storage:
-10/+60 °C
Supply voltage
AC 230 V
Nominal power
  5 VA
Housing
Wall mounting housing made of impact-resistant plastic (ABS)
W x H x D:
100 x 188 x 65 mm
Weight:
  400 g
Degree of protection:
IP 30 (EN 60529)
Switching output
Relay contact:
1 x voltage-free changeover contact
Contact rating:
AC 250 V, 2 A
Alarm sound
min. 70 dB(A)
Tanks
Plastic, white
W x H x D:
300 x 325 x 145 mm
Active volume:
4.5 l
Total volume:
10 l
outlet:
G¾ female
Degree of protection:
IP 20 (EN 60529)
approval
CE marking as per EC Construction Products Regulation 305/2011, EU 574/2014, EN 13160-1/-3 and ÜHP
Scope of delivery
  • Control unit
  • Behälter
  • Probe

AFRISO_WATCHDOG-LINE_ALARM_UNITS_EN_05-14.PDF

WATCHDOG-LINE Warngeräte

PDF
USE-AND-RESISTANCE-OIL-COMPONENTS-FLYER.PDF

Beständigkeit Ölkomponenten

PDF
LAG13KR.PDF

Leckanzeigegerät LAG-13 KR

PDF
Download

Mounting accessories
Abb.
Bezeichnung
 Sealing kit  IP 54
Sealing kit IP 54 | 43416
 mounting frame
mounting frame | 43521
 DIN rail clip
DIN rail clip | 43100
Accessories and spare parts leak detectors, leak monitoring systems and leak protection linings
Abb.
Bezeichnung
 LAG mounting kit
LAG mounting kit | 40540
 mounting kit  for 1 LAG additional container without container
mounting kit for 1 LAG additional container without container | 40539

Accessories and spare parts leak detectors, leak monitoring systems and leak protection linings
Abb.
Bezeichnung
 LAG container  white
LAG container white | 40730
 Control unit LAG-13 KR
Control unit LAG-13 KR | 40630
 Foil keypad  LAG for control units year of manufacture 1996 and later
Foil keypad LAG for control units year of manufacture 1996 and later | 43726
 Foil keypad  LAG for control units year of manufacture 2007 and later
Foil keypad LAG for control units year of manufacture 2007 and later | 43727
 LAG probe
LAG probe | 40510