Boiler safety group assembly KSG Magnum

Afriso Boiler safety group assembly KSG Magnum
Data sheet Boiler safety group assembly KSG Magnum
Afriso Data sheet Boiler safety group assembly KSG Magnum

Versions

Heat capacity Response pressure Boiler connection Part no. Remember
Boiler safety group assembly KSG Magnum Max. 200 kW 3 bar G1¼ IG 77627
Boiler safety group assembly KSG Magnum Max. 350 kW 3 bar G1½ female 77628

Blue part no. = in-stock items

Description Format Language Download / Link
Data sheet Boiler safety group assembly KSG Magnum Data sheet PDF
Afriso Data sheet Boiler safety group assembly KSG Magnum
Boiler safety group assembly KSG Magnum Operating instructions PDF
Afriso Boiler safety group assembly KSG Magnum
Complete, pre-assembled, tightness-tested boiler safety group assembly. Consisting of carrier designed as multi-way union, pressure gauge for indicating the system pressure, quick air vent and diaphragm safety valve MS. With self-sealing mounting valves for easy replacement of pressure gauge and quick air vent. The form-fit insulation is also used to package the product for safe transport.
Connection boiler
Max. 200 kW:
G1¼ IG
Max. 350 kW:
G1½ female
Operating temperature range
Max. 120 °C
Dimensions
W x H x D:
230 x 175 x 104 mm
Insulation
Polypropylene EPP
Carrier
Brass
Diaphragm safety valve MS
Inlet x outlet
Max. 200 kW:
G1 x G1¼
Max. 350 kW:
G1¼ x G1½
Seal:
PTFE sealing ring, can be rotated
Response pressure:
3 bar
Pressure gauges for heating installations
Range:
0/4 bar
Diameter:
63 mm
Connection:
G⅜ bottom
Quick air vents
Input:
G⅜
Nominal pressure:
12 bar