Thermal safety valve TAS 03

AFRISO Thermische Ablaufsicherung TAS 03 Kapillarrohr 1,3m VOR 93210 93220 object_image_56132imagemain_en AFRISO Thermische Ablaufsicherung TAS 03 Kapillarrohr 1,3m VOR 93210 93220 object_image_56132imagemain_en
Thermische Ablaufsicherung TAS 03 Kapillarrohr 1,3m
AFRISO Thermische Ablaufsicherung TAS 03 Kapillarrohr 1,3m VOR 93210 93220 object_image_56132imagemain_en
AFRISO Verschraubungsset G3/4 für TAS 03 VOR 6960 AFRISO Verschraubungsset G3/4 für TAS 03 VOR 6960
Verschraubungsset G3/4 für TAS 03
AFRISO Verschraubungsset G3/4 für TAS 03 VOR 6960
AFRISO Tauchhülse G1/2 für TAS 03 VOR 100890 AFRISO Tauchhülse G1/2 für TAS 03 VOR 100890
Tauchhülse G1/2 für TAS 03
AFRISO Tauchhülse G1/2 für TAS 03 VOR 100890
AFRISO Thermische Ablaufsicherung TAS 03 Kapillarrohr 1,3m VOR 93210 93220 object_image_56132imagemain_en
AFRISO Verschraubungsset G3/4 für TAS 03 VOR 6960
AFRISO Tauchhülse G1/2 für TAS 03 VOR 100890
Data sheet Thermal safety valve TAS 03
AFRISO Data sheet Thermal safety valve TAS 03

Versions

Part no. Remember
Thermal safety valve TAS 03 capillary tube 1.3 m 42415
Thermal safety valve TAS 03 capillary tube 4 m 42418
Screw connection G¾ for TAS 03 42450
Pocket G½ for TAS 03 42449

Blue part no. = in-stock items

Description Format Language Download / Link
Data sheet Thermal safety valve TAS 03 Data sheet PDF
AFRISO Data sheet Thermal safety valve TAS 03
Thermal safety valve TAS 03 Operating instructions PDF
AFRISO Thermal safety valve TAS 03
Thermal safety valve with two independent sensor systems. TAS consists of a valve housing, a valve, two independent bellow type displacement probes with liquid-filled temperature probes and a pocket. The capillary tube is protected by a flexible metal hose. TAS is connected to the hot water outlet of the water heater or to the inlet of the safety heat exchanger. If the response temperature is exceeded, the valve is opened by the thermal probe and cooling water from the mains water supply system is supplied to keep the system from exceeding the maximum operating temperature. Correct operation of TAS can be verified quickly and easily by simply pressing the valve head.
Operating pressure
Max. 10 bar
Operating temperature range
Ambient:
Max. 80 °C at valve
Operating temperature:
5/115 °C
Short-term operating temperature:
Max. 125 °C at capillary tube and probe
Response temperature:
99 °C
Blow-off capacity
> 2.4 m³/h at 110 °C and ∆p = 1 bar
Connection
2 x G¾ female
Connection immersion pipe
G½ male
Dimensions
Immersion pipe length:
146 mm
Capillary tube length:
1,300 mm or 4,000 mm
Installation length:
146 mm to boiler
Material
Housing:
Hot-pressed brass
Stem:
Brass, nickel-plated