Thermostats with housing GTK With capillary tube

Afriso Thermostats with housing GTK With capillary tube
Afriso Thermostats with housing GTK With capillary tube
Afriso Thermostats with housing GTK With capillary tube
Data sheet thermostats with housing GTK With capillary tube
Afriso Data sheet thermostats with housing GTK With capillary tube

Versions

Adjustment Operating range Capillary length Part no. Remember
Thermostat with housing GTK/7RD External 0/90 °C 1,000 mm 67421X
Thermostat with housing GTK/7RD External 0/90 °C 2,000 mm 67424X

Blue part no. = in-stock items

Description Format Language Download / Link
Data sheet thermostats with housing GTK With capillary tube Catalog page PDF
Afriso Data sheet thermostats with housing GTK With capillary tube
The temperature measured at the probe causes a change in the volume of the measuring liquid in the probe-capillary system. Electrical switching is triggered by the force acting. A thermowell allows for pressure-tight installation of the probe in various types of pressurised tanks.
Type
GTK/TC2
Operating range
0/90 °C
Tolerance
±0.4 %/10 K
Switching differential
∆T 4 ± 1 K
Setting
External
Probe
Copper
∅ 6.5 x 95 mm
Probe element
Liquid-filled
Operating temperature range
Probe:
Max. 150 °C
Housing:
Max. 80 °C
Housing
Plastic (PVC), grey (RAL 7035)
Cable entry
Plastic (PVC), black
M20 x 1.5
Capillary tube
Cu capillary tube with PVC coating, black
Length:
1,000, 2,000 mm
Degree of protection
IP40 (EN 60529)
Time constant
DIN-tested
DIN EN 14597:2012-09
Registration number:
TR/STB 1211
Electrical switching contact
Changeover contact
Contact rating
NC:
AC 250 V, 10 (2.5) A
NO:
AC 250 V, 6 (2.5) A

Options

  • Customised versions