Skip to main content
Back

STB | 67276X

Sicherheits-Temperaturbegrenzer mit Kapillarleitung

in-stock items

  • ideal for heating and process industries
  • for protection against exceeding the maximum temperature
  • no external power supply
  • manual reset

There are many application areas for safety temperature cut outs in the heating and process industries. In conventional oil-fired or gas-fired boilers, these devices are used to monitor the boiler water. The safety temperature cut outs feature a manual reset button which must be actuated for unlocking.

If the temperature at the probe increases, the measuring liquid in the measuring system expands. If the temperature exceeds a critical value, the device triggers, the voltage-free contact switches and the system is set to a defined safe state. When the temperature has decreased by approx. 15 K, the device can be unlocked and the system resumes operation.

Type
LS1
Switching point
see ordering table
Tolerance
+0 K/-6 K at 20 °C
Influence of ambient temperature
  0.25 °C/°C
Switching differential
∆T 15 ± 8 K
Fail safe
1 - 1
Probe
Copper
∅ 6.5 x 95 mm
Probe element
liquid-filled
Operating temperature range
Probe:
max. 125 °C
Housing:
max. 85 °C
Capillary tube
Cu capillary tube with PVC coating, black
Length:
1000 mm
Degree of protection
IP 00 (EN 60529)
Time constant
DIN-tested
DIN EN 14597:2012-09
registration number:
TR/STB 1211
electrical switching contact
Changeover contact
Contact rating
NC:
AC 250 V, 16 (2.5) A
NO:
AC 250 V, 0.5 A