Alarm unit for separators WGA 06

 ANW 93080  ANW 93080
 ANW 93080 <div class="gallery-information"> <b>Legend:</b> <ol> <li>Oil</li> <li>Water</li> </ol> </div>
 93080 object_image_64337imagemain_en
 VOR 19920
 VOR 19760 19940
 VOR 19760 19940
 VOR 19970
 SAL 19970
 SAR 19970
 DRU 19760 19940
 ANW 93080
Data sheet Alarm unit for separators WGA 06
AFRISO Data sheet Alarm unit for separators WGA 06

Versions

Part no. Remember
Alarm unit for separators WGA 06 without probes 53414
Probe WGA-ÖW for oil-on-water alarm 53417
Probe WGA-AS for overflow alarm 53415
Terminal box LJB 2-78-83 1 x input/1 x output 53403A
Terminal box LJB 3-78-83 2 x input/1 x output 53403B

Blue part no. = in-stock items

Description Format Language Download / Link
Data sheet Alarm unit for separators WGA 06 Data sheet PDF
AFRISO Data sheet Alarm unit for separators WGA 06
Alarm units WGA for separators Alarm units PDF
AFRISO Alarm units WGA for separators
Alarm unit for separators WGA 02, WGA 03, WGA 04, WGA 05, WGA 06 Declaration of Conformity PDF
AFRISO Alarm unit for separators WGA 02, WGA 03, WGA 04, WGA 05, WGA 06
WGA 06 consists of an evaluation unit and a capacitance probe (WGA-ÖW or WGA-AS). The control unit is equipped with 2 relay outputs, visual and audible alarms as well as Test and Acknowledge buttons. Either the floating probe WGA-ÖW or the fixed probe WGA-AS can be connected. WGA-ÖW floats on the surface of the water in the shaft and generates an alarm signal when an oil, grease or petrol layer of at least 15 mm has built up. WGA-AS is mounted above the constant level of the separator or the retention tank. An alarm is triggered when the maximum level is reached. The control unit monitors the probes for short circuits or line interruptions.
Operating temperature range
Medium:
0/60 °C
Ambient:
-25/+50 °C
Supply voltage
AC 230 V
Power input
Approx. 2 VA
Switching outputs
Relay contact:
2 voltage-free changeover contacts, 1 can be acknowledged
Contact rating:
AC 250 V, 5 A, 100 VA
Visual indication
1 green LED normal operation,
1 red LED alarm,
1 red LED fault
Audible alarm
Integrated piezo-buzzer, can be acknowledged
Function test
By means of test button
Housing
Wall mounting housing made of impact-resistant plastic (polycarbonate)
W x H x D:
175 x 125 x 75 mm
Degree of protection:
IP 65 (EN 60529)
Ex approval
Ex II (1) G [Ex ia] IIC
Floating probe WGA-ÖW (oil-on-water)
Measuring principle:
Capacitance
L x ⌀:
120 x 370 mm
Cable length:
5 m, PVC, oil-resistant
Ex approval:
Ex II 1 G Ex ia IIA T5 Ga
Probe WGA-AS (overflow)
Measuring principle:
Capacitance
L x ⌀:
81 x 82 mm
Cable length:
5 m, PVC, oil-resistant
Ex approval:
Ex II 1 G Ex ia IIA T5 Ga
Connection probe – control unit
Max. 300 m, depending on line resistance
Scope of delivery
  • Control unit
  • Without probes